Bowden Installation Instructions
Bowden Controllers/ Wire & Casing / B-Kits
YR-IOM-Bowden 9-2018
Step 1 Run Wire
1. Run the casing from the location where the
controller will be to the damper.
A. It should be as straight as practical and
Should be secured to the building
structure at least every 5 feet.
B. Any turns should have at least a 3 foot
radius in order to ease the inner wire
through the turn.
C. Limit cable length to no more than 50 feet.
For a longer reach use Young Regulator
Electronic Balancing Dampers.
2. Casing can be cut to length with a pair of wire
cutters.
3. Feed the inner wire through the casing. It
should slide easily.
4. Leave at least 3” of inner wire on each end.
Step 2 Assemble the 270 Controller
1. Rotate the control shaft counter-clockwise until
the rack is in the full-up position. Then return
clockwise two clicks.
2. Secure the outer casing in the casing clamp.
3. Install stainless inner-wire into the hole in the
wire stop. The washer must be between the
controller rack gear and the hole. (See Figure 3)
4. Tighten the screw until the wire starts to bend.
5. Install controller to termination using the
mounting bracket nut.
6. Install the mounting bracket with the
controller to a ceiling joist, plenum, diuser or
access panel.
Nomenclature Controller Damper
Damper Installation on Reverse
Damper Shell
Angle Bracket
Shaft
Hub
Casing Coupling
Bowden Casing
& Wire
Figure 2 5020CC Damper
Bowden Casing & Wire
Casing Clamp
Wire Stop
Rack Gear
Pinion Gear
Mounting Bracket Nut
Mounting Bracket
Control Shaft
Figure 1 270-275 Termination
Wire Stop
Inner Wire
Thumb Screw
Figure 3 Wire Stop Closeup
Wire Stop
Rack Gear Arm
Screw
Inner Wire
Washer
Step 3 Connect the Damper
1. Slide angle bracket over the shaft.
2. Align the angle bracket perpendicular to the damper shell and
fasten securely to the damper shell.
3. Slide the hub onto the shaft.
4. Rotate the shaft until the damper is fully closed.
5. Orient the hub so that it is 45
o
above the horizontal. (a little past
10:00 on a clock face) fasten the two set screws securely with a
1/8” allen wrench.
6. Install the casing coupling to the middle hole in the bottom of
the angle bracket. Secure with the keps nut.
7. Slide the inner wire through the casing coupling then through
the wire stop in the hub. Push the casing into the coupling until
it bottoms out (approx. 0.5”). Tighten the thumb screw securely.
8. Thread the inner wire through the wire stop attached to the
hub. (This is the same as on the controller without a washer.)
9. Conrm the Hub is positioned as shown in gure 4.
10. Tighten the wire stop on the hub.
11. Conrm proper operation of the damper by exercising the
control from full opn to full closed.
Installation Validation
1. Rotate the controller clockwise with the 030-12 wrench. It should move freely. If it is Hard to turn? - Check the
path of the casing. Ease any turns, ensure it is not moving as the inner wire tries to move up and down.
2. When the controller is rotated full clockwise the damper should be full open. If it is Not Fully Open? - Adjust
starting position of the hub. Release the inner wire and adjust the hub position on the shaft.
3. Cut o any excess inner wire.
Ceiling Terminations Description Application
270-275 Rack and Pinion Controller w/angle bracket Inside plenums, atop square diusers, behind
grille, above a drop ceiling or access panel
270-275 PH As above, adjusted with phillips head screwdriver Inside plenums or above drop ceilings
270-275ML Angle bracket with extended control shaft Inside plenums with Ice Tong style diusers
270-301 Ceiling cup and 3” cover Embedded in a Sheetrock ceiling
270-301BC As above, with bracket to fasten cup to stud Embedded in a Sheetrock ceiling
270-301EZ Angle bracket and 3” cover plate Above any ceiling
270-315 Cup and 2.25” threaded cap Higher security cover
270-315BC Cup, 2.25” threaded cap & 3” cover plate Embedded in a Sheetrock ceiling
270-896 “C” bracket, screw cap 1” head Embedded in a Sheetrock ceiling
4-Port Four Position Balancing Station Bring all of the cables for an area to one place
Ceiling Terminations Description Application
270-302 Cup and Cover plate - wall mount Embedded in a plastered wall
270-700 4x4 box with Stainless Cover and attractive adjustment knob Wall mount “Manual Thermostat”
270-896LO “C” bracket, screw cap 1” head - Wall mount Embedded in a plastered wall
B-Kits Shaft Size Application
270-XXXB 1/2” round or 3/8” square shafts Dampers by Others
270-XXXQ 5/16” round or 1/4” square shafts Dampers by Others
Steps 1 - 5 for B-Kits
Dampers by Others
45
o
Figure 4 - Damper Hardware
5020CC
Ceiling Terminations
Bowden Cable Controls
270-275 270-275PH 270-275ML 270-896
270-301 Cutaway 270-301EZ 270-315 Cutaway
4-Port Balancing Station
Wall Terminations
Bowden Cable Controls
270-700 “Manual Thermostat”
with 5020CC
270-302 Wall Cup and Cover 270-896LO Wall Controller
Damper
Family
Description Direction of
Operation
5020CC Round Exterior Bowden Push to Close
5020CC2 Round Interior Bowden Push to Open
820ACC OBD Bottom mount Bowden Push to Close
830ACC OBD Exterior Shaft Bowden Push to Close
Bowden Cable Controls
Functional Drawing
270-301 Concealed Cup
Room view w/o cover
Inset 270-301 Section View